![]() |
||
| Michigan.gov Home | SOAHR Home | Site Map | Contact SOAHR | |
History: 1979 AC; 1981 AACS; 2004 AACS; 2008 AACS. R 408.30419 Stadiums. Rule 419. Section 1008.2.1 of the code is amended to read as follows: 1008.2.1. Stadiums. Panic hardware is not required on gates surrounding stadiums where such gates are under constant immediate supervision while public is present, and further provided that safe dispersal areas based on 3 square feet (0.28 m2) per occupant are located between the fence and enclosed space. Such required safe dispersal areas shall not be located less than 50 feet (15 240 mm) from the enclosed space. History: 1979 AC; 1981 AACS; 2004 AACS; 2008 AACS. R 408.30420 Rescinded. History: 1979 AC; 1981 AACS. R 408.30421 Emergency escape and rescue. Rule 421. Section 1026.1 of the code is amended to read as follows: 1026.1 General. In addition to the means of egress required by this chapter, provisions shall be made for emergency escape and rescue in group R as applicable in section 101.2, classrooms greater than 250 feet2 (23.2 m2) in group E, and group I-1 occupancies. Basements and sleeping rooms below the fourth story above grade plane shall have at least 1 exterior emergency escape and rescue opening in accordance with this section. Where basements contain 1 or more sleeping rooms, emergency egress and rescue openings shall be required in each sleeping room, but shall not be required in adjoining areas of the basement. Such opening shall open directly into a public street, public alley, yard, or court. Exceptions: 1. In other than group R-3 occupancies as applicable in section 101.2, buildings equipped throughout with an approved automatic sprinkler system in accordance with section 903.3.1.1 or 903.3.1.2. 2. In other than group R-3 occupancies as applicable in section 101.2, sleeping rooms provided with a door to a fire-resistance-rated corridor having access to 2 remote exits in opposite directions. 3. The emergency escape and rescue opening is permitted to open onto a balcony within an atrium in accordance with the requirements of section 404, provided the balcony provides access to an exit and the dwelling unit or sleeping unit has a means of egress that is not open to the atrium. 4. Basements with a ceiling height of less than 80 inches (2032 mm) shall not be required to have emergency escape and rescue windows. 5. High-rise buildings in accordance with section 403. 6. Emergency escape and rescue openings are not required from basements or sleeping rooms which have an exit door or exit access door that opens directly into a public street, public alley, yard, egress court, or to an exterior exit balcony that opens to a public street, public alley, yard, or egress court. 7. Basements without habitable spaces and having not more than 200 square feet (18.6 square meters) in floor area shall not be required to have emergency escape windows. History: 1979 AC; 1981 AACS; 2004 AACS; 2008 AACS. R 408.30422 Rescinded. History: 1979 AC; 1981 AACS. R 408.30423 Rescinded. History: 1979 AC; 1981 AACS. R 408.30427 Barrier free design for buildings, structures, and improved areas. Rule 427. Sections 1101.2 and 1109.7 of the code are amended and section 1103.2.16 is added to the code to read as follows: 1101.2 Design. Buildings and facilities shall be designed and constructed to be accessible in accordance with 1966 PA 1, MCL 125.1351 to 125.1356, this code and ICC/ANSI A 117.1, except sections 611 and 707. 1109.7 Lifts. Platform (wheelchair) lifts are permitted to be a part of a required accessible route in new construction where indicated in items 1 to 10. Platform (wheelchair) lifts shall be installed in accordance with the Michigan elevator code, R 408.7001 to R 408.8695. 1. An accessible route to a performing area and speakers' platforms in occupancies in group A. 2. An accessible route to wheelchair spaces required to comply with the wheelchair space dispersion requirements of sections 1108.2.2 to 1108.2.4. 3. An accessible route to spaces that are not open to the general public with an occupant load of not more than 5. 4. An accessible route within a dwelling or sleeping unit. 5. An accessible route to wheelchair seating spaces located in outdoor dining terraces in A-5 occupancies where the means of egress from the dining terraces to a public way are open to the outdoors. 6. An accessible route to jury boxes and witness stands; raised courtroom stations including judges' benches, clerks' stations, bailiffs' stations, deputy clerks' stations and court reporters' stations; and to depressed areas such as the well of the court. 7. An accessible route to load and unload areas serving amusement rides. 8. An accessible route to play components or self contained play structures. 9. An accessible route to team or player seating areas serving areas of sport activity. 10. An accessible route where existing exterior site constraints make use of a ramp or elevator infeasible. 1103.2.16. Military, fire service, and police facilities. Housing, bathing, toilet, training, and storage areas intended for use and occupancy exclusively by military, fire service, police, or security personnel required to be physically agile are not required to be accessible. History: 1979 AC; 1981 AACS; 1985 AACS; 1987 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30427a Rescinded. History: 1987 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS. R 408.30427b Rescinded. History: 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS. R 408.30427c Rescinded. History: 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS. R 408.30427d Rescinded. History: 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS. R 408.30427e Rescinded. History: 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS. R 408.30428 Rescinded. History: 1979 AC; 1981 AACS; 1985 AACS; 1987 AACS; 1992 AACS; 1995 AACS. R 408.30429 High-rise buildings. Rule 429. Sections 403.1, 403.13, 907.2.12, and 907.8.2 of the code are amended to read as follows: 403.1. Applicability. The provisions of this section shall apply to buildings having the occupied floors located more than 55 feet (16764 mm) above the lowest level of fire department vehicle access. Exception: The provisions of this section shall not apply to the following buildings and structures: 1. Airport traffic control towers in accordance with section 412 of the code. 2. Open parking garages in accordance with section 406.3 of the code. 3. Buildings with an occupancy in group A-5 in accordance with section 303.1 of the code. 4. Low-hazard special industrial occupancies in accordance with section 503.1.1 of the code. 5. Buildings with an occupancy in group H-1, H-2, or H-3 in accordance with section 415 of the code. 6. Existing buildings having occupied floor levels not more than 75 feet (22860 mm) above the lowest level of fire department vehicle access where the local unit of government complies with the following: 6.1. The local unit of government has a municipal fire department with an ISO rating of 3 or lower, employing a full-time career fire fighting staff. 6.2. The governing body of the local unit of government has passed a resolution affirming the use of this exception and filed that resolution with the department of labor & economic growth, bureau of construction codes. 403.13. Smokeproof exit enclosures. Every required stairway serving floors more than 55 feet (16764 mm) above the lowest level of fire department vehicle access shall comply with sections 909.20 and 1020.1.7 of the code. 907.2.12. High-rise buildings. Buildings having floors used for human occupancy located more than 55 feet (16764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communication system in accordance with section 907.2.12.2 of the code. Exceptions: 1. Airport traffic control towers in accordance with sections 412 and 907.2.22 of the code. 2. Open parking garages in accordance with section 406.3 of the code. 3. Buildings with an occupancy in group A-5. 4. Low-hazard special occupancies in accordance with section 503.1.1 of the code. 5. Buildings with an occupancy in group H-1, H-2, or H-3 in accordance with section 415 of the code. 907.8.2. High-rise buildings. In buildings used for human occupancy that have floors located more than 55 feet (16764 mm) above the lowest level of fire department vehicle access, a separate zone by floor shall be provided for all of the following types of alarm-initiating devices where provided: 1. Smoke detectors. 2. Sprinkler water-flow devices. 3. Manual fire alarm boxes. 4. Other approved types of automatic fire detection devices or suppression systems. History: 1979 AC; 1981 AACS; 1985 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS; 2008 AACS. R 408.30429a Compliance. Rule 429a. The code is amended by adding sections 3410.1 and 3410.2 as follows: 3410.1 Compliance. The provisions of this section are intended to maintain or increase the current degree of public safety, health, and general welfare in existing buildings while permitting repair, alteration, addition, and change of occupancy without requiring full compliance with chapters 2 through 33 of the code, or sections 3401.3 through 3407, except where compliance with other provisions of the code is specifically required in this section. Exception: Buildings made to comply with the provisions of the Michigan rehabilitation code for existing buildings, R 408.30551 to R 408.30577, shall be deemed to comply with the requirements of the code. 3410.2 Applicability. Structures existing before November 6, 1974, in which work involving additions, alterations, or changes of occupancy shall be made to conform to the requirements of this section or the provisions of sections 3402 to 3406 of the code. The provisions in sections 3410.2.1 to 3410.2.5 of the code shall apply to existing occupancies that will continue to be, or are proposed to be, in groups A, B, E, F, M, R, S, and U. These provisions shall not apply to buildings that have occupancies in group H or I. History: 2002 AACS; 2004 AACS. R 408.30430 Liquefied petroleum gas distribution facilities. Rule 430. Section 415.6.3 of the code is amended to read as follows: 415.6.3. Liquefied petroleum gas distribution facilities. The design and construction of propane, butane, propylene, butylene, and other liquefied petroleum gas distribution facilities shall conform to the applicable provisions of the Michigan liquified petroleum gas code, R 29.3801 to R 29.4035. The storage and handling of liquefied petroleum gas systems shall conform to the international fire code listed in chapter 35. The design and installation of piping, equipment, and systems that utilize liquefied petroleum gas shall be in accordance with the international fuel gas code listed in chapter 35. Liquefied petroleum gas distribution facilities shall be ventilated in accordance with the Michigan mechanical code, R 408.30901 to R 408.30998, and the requirements of the Michigan rules for the storage and handling of flammable and combustible liquids, R 29.4101 to R 29.5516. History: 1979 AC; 1981 AACS; 1985 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS; 2008 AACS. R 408.30431 Rescinded. History: 1979 AC; 1981 AACS; 1985 AACS. R 408.30432 Flammable and combustible liquids. Rule 432. Section 415.6.2 of the code is amended to read as follows: 415.6.2. Flammable and combustible liquids. The storage, handling, processing, and transporting of flammable and combustible liquids shall be in accordance with the Michigan mechanical code, R 408.30901 to R 408.30998, and the international fire code listed in chapter 35, and the requirements of the Michigan rules for the storage and handling of flammable and combustible liquids, R 29.4101 to R 29.5516. History: 1979 AC; 1981 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS; 2008 AACS.AACS. R 408.30433 Rescinded. History: 1979 AC; 1981 AACS; 1985 AACS; 1987 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 1998-2000 AACS. R 408.30434 Rescinded. History: 1981 AACS; 1985 AACS; 1988 AACS; 1992 AACS. R 408.30437 Truss design drawings. Rule 437. Section 2303.4.1.2 of the code is amended to read as follows: 2303.4.1.2 Truss design drawings. Truss construction documents shall be prepared by a registered design professional and shall be provided to the building official and approved prior to installation. These construction documents shall include, at a minimum, the following information. Truss shop drawings shall be provided with the shipment of trusses delivered to the job site. 1. Slope or depth, span and spacing. 2. Location of joints. 3. Required bearing widths. 4. Design loads as applicable. 5. Top chord live load (including snow loads). 6. Top chord dead load. 7. Bottom chord live load. 8. Bottom chord dead load. 9. Concentrated loads and their points of application. 10. Controlling wind and earthquake loads. 11. Adjustments to lumber and metal connector plate design value for conditions of use. 12. Each reaction force and direction. 13. Metal connector plate type, size, thickness or gage, and the dimensioned location of each metal connector plate except where symmetrically located relative to the joint interface. 14. Lumber size, species, and grade for each member. 15. Connection requirements are required for all of the following: a. Truss to truss girder. b. Truss ply to ply. c. Field species. 16. Calculated deflection ratio or maximum deflection for live and total load. 17. Maximum axial compression forces in the truss members to enable the building designer to design the size, connections, and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss construction documents or on supplemental documents. 18. Required permanent truss member bracing location. History: 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30442 Automatic sprinkler systems. Rule 442 . Section 903.2.7 of the code is amended to read as follows: 903.2.7. Group R. An automatic sprinkler system installed in accordance with section 903.3 shall be provided throughout all buildings with a Group R fire area. Exception: Camp buildings in remote areas without municipal water supply that meet all of the following: 1. Not more than 1 story, 2000 square feet (186 m2) and 25 occupants. 2. Are used not more than 5 months in a year. 3. Shall be provided with not less than 2 exits in compliance with section 1019. 4. Shall not be provided with cooking equipment. 5. Provided with a manual fire alarm system and smoke alarms throughout in compliance with NFPA 72 as listed in chapter 35. For cabins sleeping 4 or fewer occupants only, smoke alarms are required. 6. Storage and equipment rooms shall be protected by a 1-hour fire partition. 7. Compliance with all applicable requirements of the code. History: 1979 AC; 1981 AACS; 2008 AACS. R 408.30443 Masonry. Rule 443. Section 1405.3.2 of the code is amended to read as follows: 1405.3.2. Masonry. Flashing and weep holes shall be located in the first course of masonry above finished ground level above the foundation wall or slab; at the heads of windows, doors, and other wall openings; at window sills and at other points of support including structural floors, shelf angles, and lintels where anchored veneers are designed in accordance with section 1405.5. Flashing shall extend to, or beyond, the finished face of the wall. History: 1979 AC; 1981 AACS; 1985 AACS; 1987 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2004 AACS. R 408.30444. Rescinded. History: 1979 AC; 1981 AACS; 1987 AACS; 1992 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30445 Automatic sprinkler systems. Rule 445. Section 903.2.10.3 of the code is amended to read as follows: 903.2.10.3. Buildings more than 30 feet in height. An automatic sprinkler system shall be installed throughout a building that has a floor level which has an occupant load of 30 or more occupants and which is located 30 feet or more above the lowest level of fire department vehicle access. Exceptions: 1. Airport control towers. 2. Open parking structures. 3. Occupancies in group F-2. 4. Existing buildings having occupied floor levels not more than 55 feet in height above the lowest level of fire department vehicle access, where the local unit of government complies with the following parameters: 4.1. The local unit of government having a municipal fire department with an ISO rating of 3 or lower, employing a full time career fire fighting staff. 4.2. The governing body of the local unit of government has passed a resolution affirming the use of this exception and filed that resolution with the department of labor & economic growth, bureau of construction codes and fire safety. History: 1979 AC; 1981 AACS; 1987 AACS; 1992 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2004 AACS. R 408.30446 Smoke alarm locations. Rule 446. Sections 907.2.10.1.2.1 and 907.2.10.1.2.2 are added to the code as follows: 907.2.10.1.2.1 Smoke alarm locations in existing buildings constructed before November 6, 1974. Within each dwelling unit or sleeping unit, a single-station smoke alarm shall be installed in the following locations: 1. In each sleeping room or each area directly outside the sleeping room. 2. On each floor level including the basement level. For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than 1 full story below the upper level. Section 907.2.10.1.2.2 Equipment requirements. 907.2.10.1.2.2. The required equipment for smoke alarms shall consist of the following: 1. Installation. Smoke alarm devices shall be listed and installed in accordance with the manufacturer's installation requirements, the provisions of the code, and the provisions of NFPA 72 as listed in chapter 35. 2. Power Source. The equipment shall be operable by power from 1 of the following primary sources: a. The building wiring provided the wiring is served from a commercial source and is equipped with a battery backup. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection. b. A non-rechargeable battery able to power the smoke alarm in the normal condition for a life of 5 years. c. A rechargeable battery, with proper charging, able to power the alarm for a life of 5 years. d. A commercial use alarm system with battery backup listed and approved in accordance with the commercial fire warning equipment provisions of NFPA 72, as adopted by reference in this rule. 3. Audible Alarm Notification. The activation of the alarm signal shall produce a sound that is audible in all occupiable dwelling areas. 4. Testing and Maintenance. The owner of a dwelling unit, in which required or optional fire detection or fire protection systems equipment is installed, shall be responsible for the proper operation, testing, and maintenance of the equipment in accordance with the manufacturer's instructions included with the equipment. The occupant of rental dwelling units shall be responsible for the periodic operational testing and periodic cleaning of the installed equipment within the rental unit in accordance with the testing instructions provided in the manufacturer's instructions for the equipment. If the system fails, breaks, or is out of service, it shall be repaired and functional within 30 days. Exception: Smoke alarms and devices installed in buildings constructed before November 6, 1974 where an installation was approved by the appropriate enforcing agency under regulations in effect at the time of the installation shall be considered to comply with the provisions of the code. History: 1981 AACS; 1985 AACS; 2005 AACS; 2008 AACS. R 408.30447 Smokeproof enclosures. Rule 447. Section 1020.1.7 of the code is amended to read as follows: 1020.1.7. Smokeproof enclosures. In buildings required to comply with section 403 or 405 of the code, each of the exits of a building that serves stories where the floor surface is located more than 55 feet (16764 mm) above the lowest level of fire department vehicle access or more than 30 feet (9144 mm) below the level of exit discharge serving such floor levels shall be a smokeproof enclosure or pressurized stairway in accordance with section 909.20 of the code. History: 1981 AACS; 1985 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30448 Electrical. Rule 448. Sections 2701.1, 2702.1, and 2702.2.6 of the code are amended to read as follows: 2701.1 Scope. This chapter governs the electrical components, equipment, and systems used in buildings and structures covered by the code. Electrical components, equipment, and systems shall be designed and constructed in accordance with the Michigan electrical code, R 408.30801 to R 408.30880. 2702.1. Installation. Emergency and standby power systems shall be installed in accordance with the Michigan electrical code, R 408.30801 to R 408.30880. 2702.2.6. Accessible means of egress platform lifts. Standby power in accordance with this section and the Michigan elevator code, R 408.7001 to R 408.8695, shall be provided for platform lifts that are part of an accessible means of egress in accordance with section 1007.5 of the code. History: 1979 AC; 1981 AACS; 1987 AACS; 1992 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2008 AACS. R 408.30448a Rescinded. History: 1992 AACS; 1995 AACS. R 408.30448b Rescinded. History: 1992 AACS; 1995 AACS. R 408.30448c Rescinded. History: 1992 AACS; 1995 AACS. R 408.30448d Ground snow loads. Rule 448d. Figure 1608.2 of the code is amended to read as follows:
Figure corresponds to rule in PDF format
R 408.30448d: Figure 1608.2
History: 1992 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2004 AACS. R 408.30449 Frost protection. Rule 449. Section 1805.2.1 of the code is amended to read as follows: 1805.2.1. Frost protection. Except where otherwise protected from frost, foundation walls, piers, and other permanent supports of buildings and structures shall be protected from frost by at least one of the following methods: 1. Extending not less than 42 inches below finish grade. 2. Constructing in accordance with ASCE-32 listed in chapter 35. 3. Erecting on solid rock. Exceptions: 1. Free-standing buildings meeting all of the following conditions shall not be required to be protected: a. Classified in importance category I (see table 1604.5). b. Area of 400 square feet (37 m2) or less. c. Eave height of 10 feet (3048 mm) or less. 2. Upon evidence of the existence of any of the following conditions, the building official may modify the footing depth accordingly: a. Freezing temperatures. b. Soil type. c. Groundwater conditions. d. Snow depth experience. e. Exposure to the elements. f. Other specific conditions identified by the building official that may affect the foundation system. Footings shall not bear on frozen soil unless such frozen condition is of a permanent character. History: 1979 AC; 1981 AACS; 1985 AACS; 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30449a Rescinded. History: 1992 AACS; 1995 AACS. R 408.30451 Rescinded. History: 1985 AACS; 1988 AACS; 1992 AACS; 1995 AACS. R 408.30451a Rescinded. History: 1992 AACS; 1995 AACS. R 408.30451b Rescinded. History: 1992 AACS; 1995 AACS. R 408.30451c. Flood loads. Rule 451c. Section 1612.4 of the code is amended and 1612.3.1, 1612.4.1, 1612.4.2, 1612.4.3, 1612.4.4, and 1612.4.5 are added to the code to read as follows: 1612.3.1. Alternate flood hazard provisions. Absent the adoption of a flood hazard map and supporting data, flood hazard areas as determined by the state under its administration of the Part 31, floodplain regulatory authority of the natural resources and environmental protection act, 1994 PA 451, MCL 324.101 to 324.90106, shall become the basis for regulation of floodplain development within the community and section 1612 shall apply to buildings and structures within those areas. 1612.4. Design and construction. Buildings and structures as defined in ASCE 24 table 1-1, listed in chapter 35, and located in flood hazard areas shall be designed and constructed in accordance with sections 1512.4.1 to 1612.4.5 of the code. 1612.4.1 Buildings and structures located in flood hazard areas subject to high velocity wave action shall be designed and constructed in accordance with flood hazard areas subject to high velocity wave action of ASCE 24 listed in chapter 35. 1612.4.2 Type II buildings located in flood hazard areas not subject to high velocity wave action shall be designed and constructed in accordance with section 2.0 basic requirements for flood hazard areas and shall have the lowest floors elevated 1 foot (305 mm) above the 100-year design flood elevation. 1612.4.3 Type III and IV buildings located in flood hazard areas not subject to high velocity wave action shall be designed and constructed in accordance with section 2.0 basic requirements for flood hazard areas and shall have the lowest floors elevated 1 foot (305 mm) above the 500-year flood level. 1612.4.4 If the lowest floor of nonresidential buildings and structures as defined in ASCE 24 listed in chapter 35 are located in flood hazard areas and are not elevated as required in accordance with sections 1612.4.2 and 1612.4.3, Type II buildings shall be flood proofed to 1 foot above the design flood elevations and Type III & IV buildings shall be flood proofed to 1 foot above the 500-year flood level in accordance with the flood proofing requirements contained in ASCE 24 listed in chapter 35. 1612.4.5 Crawl space interior floor grade elevation shall comply with section 1807.1.2.1 of the code. History: 1992 AACS; 1995 AACS; 2001 AACS; 2008 AACS. R 408.30451d Rescinded. History: 1992 AACS; 1995 AACS. R 408.30451e Rescinded. History: 1992 AACS; 1995 AACS; 1998-2000 AACS. R 408.30452 Rescinded. History: 1985 AACS; 1988 AACS; 1995 AACS. R 408.30453 Plumbing systems. Rule 453. Section 2901.1 of the code is amended to read as follows: 2901.1. Scope. The provisions of this chapter and the Michigan plumbing code, R 408.30701 to R 408.30796, shall govern the erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of, plumbing equipment and systems. Plumbing systems and equipment shall be constructed, installed, and maintained in accordance with the Michigan plumbing code, R 408.30701 to R 408.30796. History: 1985 AACS; 1988 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS. R 408.30454 Rescinded. History: 1985 AACS; 1988 AACS; 1995 AACS; 1998-2000 AACS. R 408.30455 Rescinded. History: 1985 AACS; 1988 AACS; 1995 AACS; 1998-2000 AACS. R 408.30456 Rescinded. History: 1985 AACS; 1988 AACS; 1995 AACS; 1998-2000 AACS. Editor's note: Former R 408.30456 was rescinded by 1979 ACS 8, Eff. Dec. 16, 1981. R 408.30457 Mechanical systems. Rule 457. Section 2801.1 of the code is amended to read as follows: 2801.1. Scope. Mechanical appliances, equipment, and systems shall be constructed, installed, and maintained in accordance with the Michigan mechanical code, R 408.30901 to R 408.30998, and the international fuel gas code listed in chapter 35. Masonry chimneys, fireplaces, and barbeques shall comply with the Michigan mechanical code, R 408.30901 to R 408.30998, and chapter 21 of the code. History: 1985 AACS; 1988 AACS; 1995 AACS; 2001 AACS; 2008 AACS. R 408.30458 Elevators and conveying systems. Rule 458. Sections 3001.1, 3001.2, 3001.4, 3002.5, 3002.6, 3003.1, 3003.2, and 3004.4, of the code are amended and sections 3001.2.1, 3001.2.2, 3003.1.5 and 3004.5 are added to the code to read as follows: 3001.1. Scope. The design, construction, installation, alteration, and repair of elevators and conveying systems and their equipment shall conform with the requirements of the Michigan elevator laws and rules, MCL 408.801 to 408.824, MCL 338.2151 to 338.2160, and R 408.7001 to R 408.8695 and this chapter. Installation or construction in flood hazard areas established in section 1612.3 shall comply with ASCE 24 listed in chapter 35. 3001.2. Other devices. Other devices shall conform to the requirements of sections 3001.2.1 and 3001.2.2 of the code. 3001.2.1. Conveyors. Conveyors and related equipment shall conform to the requirements of ASME B20.1 listed in chapter 35. 3001.2.2. Automotive lifts. Automotive lifts shall conform to the requirements of ALI ALCTV listed in chapter 35. 3001.4. Change in use. A change in use of an elevator from freight to passenger, passenger to freight, or from 1 freight class to another freight class shall comply with the requirements of the Michigan elevator code, R 408.7001 to R 408.8695. 3002.5. Emergency doors. Where an elevator is installed in a single blind hoistway or on the outside of a building, there shall be installed in the blind portion of the hoistway or blank face of the building, an emergency door in accordance with the requirements of the Michigan elevator code, R 408.7001 to R 408.8695. 3002.6. Prohibited doors. Doors, other than hoistway doors and the elevator car door, shall be prohibited at the point of access to an elevator car. 3003.1. Standby power. In buildings and structures where standby power is required or furnished to operate an elevator, the operation shall be in accordance with sections 3003.1.1 to 3003.1.5 of the code. 3003.1.5. Lighting. Where standby power is connected to elevators, the machine room, car top, pit, and landing lighting shall be connected to the standby power source. 3003.2 Fire-fighters' emergency operation. Elevators shall be provided with phase I emergency recall operation and phase II emergency in-car operation in accordance with the requirements of the Michigan elevator code, R 408.7001 to R 408.8695. 3004.4. Plumbing and mechanical systems. Plumbing and mechanical systems shall not be located in an elevator shaft. Exception: Floor drains, sumps, and sump pumps exclusively for draining the elevator pit shall be permitted at the base of the shaft provided they are indirectly connected to the plumbing system. 3004.5. Construction at bottom of hoistway. Pits extending to the ground shall have noncombustible floors and be designed as to prevent entry of ground water into the pit. The pit floor of any hoistway not extending to the ground shall be of fire-resistive construction having a fire-resistance rating at least equal to that required for the hoistway enclosure. History: 1988 AACS; 1992 AACS; 1995 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30459 Elevators. Rule 459. Sections 1007.4 and 1607.8.1 of the code are amended to read as follows: 1007.4. Elevators. To be considered part of an accessible means of egress, an elevator shall comply with the emergency operation and signaling device requirements of the Michigan elevator code, R 408.7001 to R 408.8695. 1607.8.1. Elevators. Elevator loads shall be increased by 100% for impact and the structural supports shall be designed within the limits of deflection prescribed by the Michigan elevator code, R 408.7001 to R 408.8695. History: 1985 AACS; 1988 AACS; 1992 AACS; 2008 AACS. R 408.30460 Rescinded. History: 1979 AC; 1981 AACS; 1987 AACS; 1988 AACS; 1992 AACS. R 408.30461 Rescinded. History: 1979 AC; 1981 AACS; 1987 AACS; 1988 AACS; 2001 AACS; 2004 AACS. R 408.30475 Existing structures. Rule 475. Sections 3409.1, 3409.4 3409.6, 3409.7, 3409.8.2, 3409.8.3 and 3410.6.14 of the code are amended to read as follows: 3409.1. Scope. The provisions of sections 3409.2 to 3409.9 of the code apply to the maintenance, change of occupancy, additions, and alterations to existing buildings, including those identified as historic buildings in accordance with 1966 PA 1, MCL 125.1351 to 125.1356. Exception: Type B dwelling or sleeping units required by section 1107 are not required to be provided in existing buildings and facilities. 3409.. Change of occupancy. Unless technically infeasible, section 3409.6 of the code shall be applied in accordance with 1966 PA 1, MCL 125.1351 to 125.1356. 3409.6. Alterations. A building, facility, or element that is altered shall comply with the applicable provisions in chapter 11 of the code and ICC/ANSI A117.1 listed in chapter 35, unless technically infeasible. When compliance with this section is technically infeasible, then the alteration shall provide access to the maximum extent technically feasible. Exceptions: 1. The altered element or space is not required to be on an accessible route, unless required by section 3409.7 of the code. 2. Accessible means of egress required by chapter 10 of the code are not required to be provided in existing buildings and facilities. 3. Buildings, structures, or improved areas which exist on or before the effective date of these rules and which are in compliance with the code at the time of the issuance of the certificate of occupancy unless the alteration specifically modifies an area covered by sections 3409.7 to 3409.9.4 of the code. 4. The alteration to type A individually owned dwelling units within a group R-2 occupancy shall meet the provision for a type B dwelling unit and shall comply with the applicable provisions in chapter 11 and ICC/ANSI A 117.1 as listed in chapter 35. 3409.7. Alterations affecting an area containing a primary function. When an alteration affects the accessibility to, or contains an area of primary function, then the route to the primary function area shall be accessible. The accessible route to the primary function shall include accessible toilets and drinking fountains serving the area of the primary function. Exceptions: 1. This section does not apply to alterations limited solely to windows, hardware, operating controls, electrical outlets, and signs. 2. This section does not apply to alterations limited solely to mechanical systems, electrical systems, the installation or alteration of fire-protection systems, and the abatement of hazardous materials. 3. This section does not apply to alterations undertaken for the primary purpose of increasing the accessibility of an existing building, facility, or element. 3409.8.2. Elevators. Altered elements of existing elevators shall comply with the Michigan elevator code, R 408.7001 to R 408.8695 and ICC/ANSI A 117.1 as listed in chapter 35. Such elements shall also be altered in elevators programmed to respond to the same hall call control as the altered elevator. 3409.8.3. Platform lifts. Platform (wheelchair) lifts complying with ICC/ANSI A 117.1 and installed in accordance with the Michigan elevator code, R 408.7001 to R 408.8695 shall be permitted as a component of an accessible route. 3410.6.14. Elevator control. Evaluate the passenger elevator equipment and controls that are available to the fire department to reach all occupied floors. Elevator recall controls shall be provided in accordance with the Michigan elevator code, R 408.7001 to R 408.8695. Under the categories and occupancies in table 3410.6.14, determine the appropriate value and enter that value into table 3410.7 of the code under safety parameter 3410.6.14, elevator control, for fire safety, means of egress and general safety. The values shall be zero for a single-story building. History: 1985 AACS; 1988 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30476 Exterior envelope requirements. Rule 476. Section 1301.1.1 of the code is amended to read as follows: 1301.1.1. General. Buildings shall be designed and constructed in accordance with the Michigan uniform energy code, part 10 rules, R 408.31001 to R 408.31099. History: 1985 AACS; 1988 AACS; 1995 AACS; 2001 AACS. R 408.30495 Rodent proofing. Appendix F101.1 of the code is amended and F101.1.1 is added to the code to read as follows: F101.1. General. Buildings or structures and the walls enclosing habitable or occupiable rooms and spaces in which people live, sleep, or work, or in which feed, food, or foodstuff is stored, prepared, processed, served, or sold shall be constructed in accordance with this section. Other buildings are subject to these requirements as provided in section F101.1.1 of the code. F101.1.1. Additional buildings. In a community that has a vermin infestation program for the eradication of vermin enacted by local ordinance, all buildings identified within such an ordinance shall be constructed in accordance with this section. History: 1985 AACS; 1988 AACS; 2001 AACS; 2008 AACS. R 408.30495a Rescinded. History: 1985 AACS; 1988 AACS; 1995 AACS; 2004 AACS. R 408.30495b Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495c Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495d Rescinded. History: History: 1985 AACS; 1988 AACS. R 408.30495e Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495f Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495g Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495h Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495i Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495j Rescinded. History: 1985 AACS; 1988 AACS. R 408.30495k Rescinded. History: 1985 AACS; 1988 AACS. R 408.30497 Signs. Appendix H101.1.1 is added to the code and H111.1 of the code is amended to read as follows: H101.1.1. Local ordinances. A governmental subdivision that has sign regulations governing the placement, location, size, height, or setback from public right of ways shall govern such items. H111.1. Materials. Wall signs shall be constructed of materials consistent with building materials governed by the type of construction as provided in chapter 6 of the code for the building or structure. Wall signs exceeding 40 square feet (3.72 m2)in area shall be constructed of metal or other approved noncombustible material, except for nailing rails and except as provided in sections H106.1.1 and H107.1 of the code. History: 1979 AC; 1981 AACS; 2001 AACS. R 408.30499 Adoption of standards by reference; referenced codes. Rule 499. Chapter 35 of the code is amended to add the following referenced codes, which are available from the Michigan Department of Labor & Economic Growth, Bureau of Construction Codes, 2501 Woodlake Circle, Okemos, Michigan 48864: (a)Michigan Electrical Code R 408.30801 to R 408.30880,of the Michigan Administrative Code. (b)Michigan Mechanical Code R 408.30901 to R 408.30998a of the Michigan Administrative Code. (c)Michigan Plumbing Code R 408.30701 to R 408.30796 of the Michigan Administrative Code. (d)Michigan Uniform Energy Code R 408.31061 to R 408.31099 of the Michigan Administrative Code. (e)Michigan Elevator Code R 408.7001 to R 408.8695 of the Michigan Administrative Code. (f)Michigan Boiler Code R 408.4001 to R 408.5507 of the Michigan Administrative Code. History: 1985 AACS; 1988 AACS; 1995 AACS; 1998-2000 AACS; 2001 AACS; 2004 AACS; 2008 AACS. R 408.30499a Rescinded. History: 1998-2000 AACS; 2001 AACS. RESIDENTIAL CODE R 408.30501 Appointment. Rule 501. Section R103.2 of the code is amended to read as follows: R103.2. "Building official" means the person who is appointed and employed by a governmental subdivision, who is charged with the administration and enforcement of the state codes specified in R 408.30499, and who is registered in compliance with 1986 PA 54, MCL 338.2301 et seq. 2001 AACS. R 408.30502 Building inspector. Rule 502. Section R103.3 of the code is amended to read as follows: R103.3. "Building inspector" means the person who is appointed and employed by a governmental subdivision, who is charged with the administration and enforcement of the state codes specified in R 408.30499, and who is registered in compliance with 1986 PA 54, MCL 338.2301 et seq. 2001 AACS. R 408.30503 Approved materials and equipment. Rule 503. Sections R104.9 of the code is amended to read as follows: R104.9. Approved materials and equipment. Materials, equipment, and devices shall be constructed or installed in accordance with approvals granted under the act or by the building official. The building official shall review reports prepared by recognized evaluation services and determine if the intent of the code is met. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30504 Alternative materials, design, and methods of construction and equipment. Rule 504. Section R104.11 of the code is amended to read as follows: R104.11. Alternative materials, design, and methods of construction and equipment. The provisions of the code are not intended to prevent the installation of any material or to prohibit any design or method of construction not specifically prescribed by the code, if the alternative has been approved. An alternative material, design, or method of construction shall be approved where the building official finds that the proposed design is satisfactory and complies with the intent of the provisions of the code, and that the material, method, or work offered is, for the purpose intended, at least the equivalent of that prescribed in the code. Compliance with the specific performance-based provisions of the Michigan building, R 408.30401 to R 408.30547, electrical, R 408.30801 to R 408.30880, mechanical, R 408.30901 to R 408.30998 and plumbing, R 408.30701 to R 408.30796, codes instead of specific requirements of the code shall also be permitted as an alternate. History: 2001 AACS.; 2008 AACS. R 408.30505 Work exempt from permit.. Rule 505. Section R105.2 of the code is amended to read as follows: R105.2. Work exempt from permit. Exemption from the permit requirements of the code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of the code or any other laws or ordinances of this jurisdiction. Permits are not required for any of the following: (a) Building permits shall not be required for any of the following: (i) One-story detached accessory structures, if the floor area does not exceed 200 square feet (18.58 m2). (ii) A fence that is not more than 6 feet (1829 mm) high. (iii) A retaining wall that is not more than 4 feet (1219 mm) in height measured from the bottom of the footing to the top of the wall, unless supporting a surcharge. (iv) A water tank supported directly upon grade if the capacity is not more than 5,000 gallons ( 18 927 L) and the ratio of height to diameter or width is not greater than 2 to 1. (v) A sidewalk or driveway that is not more than 30 inches (762 mm) above adjacent grade and is not over any basement or story below. (vi) Painting, papering, tiling, carpeting, cabinets, counter tops, and similar finish work. (vii) A prefabricated swimming pool that is less than 24 inches (610 mm) deep. (viii) Swings and other playground equipment accessory to a 1- or 2-family dwelling. (ix) Window awnings supported by an exterior wall which do not project more than 54 inches (1372 mm) from the exterior wall and do not require additional support. (b) Electrical permits shall not be required for the following; Repairs and maintenance: A permit is not required for minor repair work, including the replacement of lamps or the connection of approved portable electrical equipment to approved permanently installed receptacles. (c) Mechanical permits shall not be required for any of the following: (i) Portable heating, cooking, or clothes drying appliances. (ii) Replacement of any minor part that does not alter approval of equipment or make the equipment unsafe. (iii) A portable heating appliance. (iv) A portable ventilation appliance. (v) A portable cooling unit. (vi) Steam, hot or chilled water piping within any heating or cooling equipment regulated by the code. (vii) Replacement of any minor part that does not alter approval of equipment or make the equipment unsafe. (viii) A portable evaporative cooler. (ix) A self-contained portable refrigeration unit that is not more than 1.5 horsepower (1119 W). (x) Portable fuel cell appliances that are not connected to a fixed piping system and are not interconnected to a power grid. (xi) Gas piping limited to 10 feet (3048 mm) in length and not more than 6 fittings. (d) Plumbing permits shall not be required for any of the following: (i) The stopping of leaks in drains, water, soil, waste or vent pipe; if any concealed trap, drainpipe, water, soil, waste or vent pipe becomes defective and it becomes necessary to remove and replace the same with new material, then the work is considered as new work and a permit shall be obtained and inspection made as provided in the code. (ii) The clearing of stoppages or the repairing of leaks in pipes, valves, or fixtures, and the removal and reinstallation of water closets, if the repairs do not involve or require the replacement or rearrangement of valves, pipes, or fixtures. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30506 Submittal documents. Rule 506. Sections R106.1 and R802.10.1 of the code are amended and section R106.1.4 and figure 802.10.1 are added to the code to read as follows: R106.1. Submittal documents. Construction documents, special inspection and structural program and other data shall be submitted in 1 or more sets with each application for a permit. The construction documents shall be prepared by or under the direct supervision of a registered design professional when required by 1980 PA 299, MCL 339.101 to 339.2721, and known as the Michigan occupational code. Where special conditions exist, the building official is authorized to require additional construction documents to be prepared by a registered design professional. R106.1.4. Truss design data. As an alternative to the submission of truss design drawings, the truss design data sheet may be provided to the building official as part of the construction documents at the time of application. Truss design drawings shall be submitted to the building official prior to truss installation as required by section R802.10.1. R802.10.1 Truss design drawings. Truss design drawings, prepared in conformance with section R802.10.1, shall be provided to the building official and approved prior to installation. The truss design data sheet, figure R802.10.1, may be provided to the building official at the time of permit application, as an alternative to design drawings as permitted in section R106.1.4. Truss design drawings shall include, at a minimum, the information specified below. Truss design drawings shall be provided with the shipment of trusses delivered to the jobsite. 1. Slope or depth, span, and spacing. 2. Location of all joints. 3. Required bearing widths. 4. Design loads as applicable. a. Top chord live load (including snow loads). b. Top chord dead load. c. Bottom chord live load. d. Bottom chord dead load. e. Concentrated loads and their points of application. f. Controlling wind and earthquake loads. 5. Adjustments to lumber and joint connector design values for conditions of use. 6. Each reaction force and direction. 7. Joint connector type and description (e.g., size, thickness, or gauge) and the dimensioned location of each joint connector except where symmetrically located relative to the joint interface. 8. Lumber size, species, and grade for each member. 9. Connection requirements for the following: a. Truss to truss girder. b. Truss ply to ply. c. Field splices. 10. Calculated deflection ratio and/or maximum description for live and total load. 11. Maximum axial compression forces in the truss members to enable the building designer to design the size, connections, and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss design drawing or on supplemental documents.
History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30507 Exhaust installation. Rule 507. Section G2439.3 (614.4) of the code is amended to read as follows: G2439.3 (614.4). Exhaust installation. Dryer exhaust ducts for clothes dryers shall terminate on the outside of the building, shall not terminate within 4 feet of a ventilated section in a soffit, and shall be equipped with a backdraft damper. Screens shall not be installed at the duct termination. Ducts shall not be connected or installed with sheet metal screws or other fasteners that will obstruct the flow. Clothes dryer exhaust ducts shall not be connected to a vent connector, vent, or chimney. Clothes dryer exhaust ducts shall not extend into or through ducts or plenums. History: 2001 AACS.; 2008 AACS. R 408.30508 Payment of fees. Rule 508. Section R108.1 of the code is amended to read as follows: R108.1. Fees. The fees prescribed in the act shall be paid to the enforcing agency of the jurisdiction before a permit to begin work for new construction, alteration, removal, demolition, or other building operation may be issued. In addition, an amendment to a permit necessitating an additional fee shall not be approved until the additional fee is paid. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30509 Frame and masonry inspection. Rule 509. Section R109.1.4 of the code is amended to read as follows: R109.1.4. Frame and masonry inspection. Inspection of framing construction shall be made after the roof, all framing, firestopping, draftstopping, and bracing are in place and after the plumbing, mechanical, and electrical rough inspections are approved. Masonry inspections shall be made after the completed installation of base course flashing as specified in section R703.7.5 of the code and water-resistive barrier as specified in section R703.2 of the code and after the masonry construction is completed. History: 2001 AACS.; 2008 AACS. R 408.30510 Use and occupancy. Rule 510. Sections R110.1 and R110.2 of the code are amended to read as follows: R110.1. Use and occupancy. A building or structure shall not be used or occupied, and a change in the existing occupancy classification of a building or structure or portion thereof shall not be made until a certificate of occupancy has been issued in accordance with the act. R110.2. Change in use. A change in the character or use of an existing structure shall not be made, except as specified in the Michigan building code, R 408.30401 to R 408.30547. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30511 Violation penalties. Rule 511. Section R113.4 of the code is amended to read as follows: R113.4. Violation penalties. It is unlawful for any person, firm, or corporation to violate a provision of the code or fail to conform with any of the requirements thereof, or erect, construct, alter, extend, repair, move, remove, demolish, or occupy any building, structure, or equipment regulated by the code, or cause work to be performed or done in conflict with or in violation of the approved construction documents or directive of the enforcing agency, or a permit or certificate issued under the code. A violator shall be assessed a fine in accordance with the act. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30512 Notice to owner. Rule 512. Section R114.1 of the code is amended to read as follows: R114.1. Notice to owner. Upon notice from the enforcing agency, work on any building or structure that is being done contrary to the code or in a dangerous or unsafe manner shall immediately cease. The notice shall be in accordance with the act. Any person who is served with a stop work order, except for work that the person is directed to perform to remove a violation or unsafe condition is subject to the penalty provisions in the act. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30513 Definitions. Rule 513. The definitions of building, registered design professional, and sunroom addition in section R202 of the code are amended, the definition of residential building type is deleted, and the definition of structure is added to section R202 to read as follows: R202. Definitions. "Building" means a combination of materials, whether portable or fixed, forming a structure affording a facility or shelter for use or occupancy by persons, animals, or property. The term does not include a building incidental to the use for agricultural purposes of the land on which the building is located if it is not used in the business of retail trade. The term shall be construed as though followed by the words "or part or parts of the building and all equipment in the building" unless the context clearly requires a different meaning. "Registered design professional" means an individual who is licensed under 1980 PA 299, MCL 339.2001 to 339.2721. "Structure" means that which is built or constructed, an edifice or building of any kind, or a piece of work artificially built up or composed of parts joined together in some definite manner. Structure does not include a structure incident to the use for agricultural purposes of the land on which the structure is located and does not include works of heavy civil construction including without limitation any of the following: (a) A highway. (b) A bridge. (c) A dam. (d) A reservoir. (e) A lock. (f) A mine. (g) A harbor. (h) A dockside port facility. (i) An airport landing facility. (j) A facility for the generation, or transmission, or distribution of electricity. Structure shall be construed as though followed by the word "or part or parts of the structure and all equipment in the structure," unless the context clearly indicates otherwise. "Sunroom addition" means a new structure with glazing in excess of 40% of the gross area of the structure's exterior walls and roof added to an existing dwelling. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30514 Means of appeal. Rule 514. Sections R112.1 and R112.3 of the code are amended to read as follows: R112.1 Means of appeal. An interested person has the right to appeal a decision of the enforcing agency to the board of appeals in accordance with the act. An application for appeal shall be based on a claim that the true intent of the code or the rules governing construction have been incorrectly interpreted, the provisions of the code do not apply, or an equal or better form of construction is proposed. The decision of a local board of appeals may be appealed to the construction code commission in accordance with the act and timeframes. Exception: Requests for barrier free design exception shall be in accordance with 1966 PA 1, MCL 125.1351 to 125.1356. 112.3 Qualifications. The board of appeals shall consist of members who are qualified in accordance with the act. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30515 Ground snow loads Rule 515. Figure R301.2(5) of the code is amended to read as follows: Figure R301.2(5) Ground Snow Loads Pg for Michigan (lb/ft2) ******* Table R301.2(5) please see attached Figure *******
Tables
corresponding to rules in PDF format
R 408.30515: Table R301.2(5)
History: 2001 AACS.; 2004 AACS. R 408.30516 Design criteria. Rule 516. Table R301.2(1) of the code is amended and figures R301.2(7) and R301.2(8) are added to the code to read as follows: TABLE R 301.2(1) CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
|
Ground Snow Load |
Wind Speedd (mph) |
Seismic Design Categoryf |
Subject to Damage From |
Winter Design Tempe |
Ice Barrier Underlayment Requiredh |
Flood Hazardsg |
Air Freezing Indexi |
Mean Annual Tempj |
||
|
Weatheringa |
Frostline depthb |
Termitec |
|
|
|
|
|
|||
|
Figure R301.2(5) |
90 |
See Sec.R301.2.2.1 & Figure R301.2(2) |
Severe |
42” See Note b |
Figure R301.2(6) |
See Note e |
Yes |
See Note g |
Figure R403.3(2) |
See footnote J |
a. Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column shall be filled in with the weathering index (i.e., "negligible", "moderate" or "severe") for concrete as determined from the weathering probability map [figure R301.2(3)]. The grade of masonry units shall be determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652 as listed in chapter 43. b. The frost line depth may be modified as provided in section R403.1.4 of the code. c. The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a history of local damage. d. The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [figure R301.2(4)]. Wind exposure category shall be determined on a site-specific basis in accordance with section R301.2.1.4 of the code. e. The winter design temperature criteria shall be taken from appendix D of the Michigan plumbing code, R 408.30701 to R 408.30796. f. Design category determined from section R301.2.2.1 of the code. g. The jurisdiction shall fill in this part of the table with (a) the date of the jurisdiction's entry into the national flood insurance program (date of adoption of the first code or ordinance for management of flood hazard areas), (b) the date(s) of the currently effective FIRM and FBFM or other flood hazard map adopted by the community, as may be amended. Absent (a) or (b), flood hazard areas as determined by the state under its administration of the Part 31, floodplain regulatory authority of the natural resources and environmental protection act, 1994 PA 451, MCL 324.101 to 324.90106, shall become the basis for regulation of floodplain development within the community and section R324 of the code shall apply to buildings and structures within those areas. h. In accordance with sections R905.2.7.1, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1 of the code, for areas where the average daily temperature in January is 25 degrees Fahrenheit (-4 degrees Celsius) or less, or where there has been a history of local damage from the effects of ice damming, the jurisdiction shall fill in this part of the table with "YES". Otherwise, the jurisdiction shall fill in this part of the table with "NO". i. The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (bf-days) from figure R403.3(2) or from the 100-year (99%) value on the national climatic data center data table "air freezing index-USA method (base 32 degrees Fahrenheit)". j. The jurisdiction shall fill in this part of the table with the mean annual temperature from the national climatic data center data table "air freezing index-USA method (base 32 degrees Fahrenheit)" at www.ncdc.noaa.gov/fpsf.html. History: 2001 AACS.; 2008 AACS. R 408.30517 Rescinded. History: 2001 AACS.; 2004 AACS. R 408.30518 Means of egress. Rule 518. Sections R311.6.4 and R311.4.2.1 are added to the code and R311.4.2 of the code is amended to read as follows: R311.6.4 Modular ramps. Modular ramp systems approved pursuant to the act are not required to comply with the requirements of section R403.1.4 of the code. R311.4.2. Door type and size. The required exit door shall be a side-hinged door not less than 3 feet (914 mm) in width and 6 feet, 8 inches (2032 mm) in height. Other exterior hinged or sliding doors shall not be less than 24 inches in width and 6 feet, 6 inches in height. R311.4.2.1. Interior doors. Interior doors shall be not less than 24 inches in width and 6 feet, 6 inches in height. Exception: Doors to areas less than 10 square feet of floor area. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30519 Treads and risers. Rule 519. Sections R311.5.3.1 and R 311.5.3.2 of the code are amended to read as follows: R311.5.3.1. Riser height. The maximum riser height shall be 8 1/4 inches (210 mm). The riser shall be measured vertically between leading edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm) R311.5.3.2. Tread depth. The minimum tread depth shall be 9 inches (229 mm). The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at a point 12 inches (305 mm) from the side where the treads are narrower. Winder treads shall have a minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the greatest winder tread depth at the 12-inch (305 mm) walk line shall not exceed the smallest by more than 3/8 inch (9.5 mm). History: 2001 AACS.; 2004 AACS. R 408.30520 Wood wall framing. Rule 520. Section R602.10.5 of the code is amended to read as follows: R602.10.5. Continuous structural panel sheathing. When continuous wood structural panel sheathing is provided in accordance with method 3 of R602.10.3 of the code, including areas above and below openings, braced wall panel lengths shall be in accordance with table R602.10.5 of the code. Wood structural panel sheathing shall be installed at corners in accordance with figure R602.10.5 of the code. The bracing amounts in table R602.10.1 of the code for method 3 shall be permitted to be multiplied by a factor of 0.9 for walls with a maximum opening height that does not exceed 85% of the wall height or a factor of 0.8 for walls with a maximum opening height that does not exceed 67% of the wall height. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30521 Elevation requirements. Rule 521. Section R324.2.1 of the code is amended to read as follows; R324.2.1. Elevation requirements. (1) Buildings and structures shall have the lowest floor including basements elevated so the lowest point of the floor's concrete or subfloor surface is 1 foot (305 mm) or more above the design flood elevation. The bottom of the lowest horizontal structural member of the floor system shall not be lower than the design flood elevation. Compliance with this elevation requirement shall be based upon measurement taken from the floor surface without the final floor covering and from the bottom of the lowest horizontal structural member of the floor system. (2) Crawl space interior floor grade elevation shall comply with R408.6 of the code. (3) Basement floors that are below grade on all sides shall be considered lowest floors and shall be elevated so that the lowest point of the floor surface is 1 foot (305 mm) or more above the design flood elevation. Compliance with this elevation requirement shall be based upon measurement taken from the floor surface without the final floor covering. Exception: Enclosed areas below the design flood elevation, including basements that have floors which are not below grade on all sides, shall meet the requirements of section R324.2.2 of the code. History: 2001 AACS.; 2004 AACS; 2008 AACS. R 408.30522 Minimum depth. Rule 522. Section R403.1.4 of the code is amended to read as follows: R403.1.4. Minimum depth. All exterior footings and foundation systems shall extend 42 inches below actual grade. Where applicable, the depth of the footings shall also conform to sections R403.1.4.1 to R403.1.4.2 of the code. Exception: Upon evidence of the existence of any of the following conditions, the building official may modify the footing depth accordingly: (a) Freezing temperatures (freezing degree days). (b) Soil type. (c) Ground water conditions. (d) Snow depth experience. (e) Exposure to the elements. (f) Other specific conditions identified by the building official that may affect the foundation system. History: 2001 AACS.; 2004 AACS; 2008 AACS. R 408.30522a Concrete and masonry foundation walls. Rule 522a. Section R404.1 is added to the code to read as follows: R404.1 Concrete and masonry foundation walls. Concrete and masonry foundation walls shall be selected and constructed in accordance with the provisions of section R404 or in accordance with ACI 318, ACI 332, NCMA TR68-A or ACI 530/ASCE 5/TMS 402 or other approved structural standards. When ACI 318, ACI 332 or ACI 530/ASCE 5/TMS 402 or the provisions of section R404 are used to design concrete or masonry foundation walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority. History:2008 AACS. R 408.30523 Rescinded. History: 2001 AACS.; 2004 AACS. R 408.30524 Michigan uniform energy code. Rule 524. Buildings shall be designed and constructed in accordance with the Michigan uniform energy code part 10 rules, R 408.31001 to R 408.31099. History: 2001 AACS.; 2004 AACS. R 408.30525 Scope. Rule 525. Section M1301.1 of the code is amended to read as follows: M1301.1. Scope. The provisions of this chapter shall govern the installation of mechanical systems not specifically covered in other chapters applicable to mechanical systems. Installations of mechanical appliances, equipment, and systems not addressed by the code shall comply with the applicable provisions of the Michigan mechanical code, R 408.30901 to R 408.30998 and the international fuel gas code. History: 2001 AACS.; 2008 AACS. R 408.30526 Sizing. Rule 526. Section M1401.3 of the code is amended to read as follows: M1401.3. Sizing. Heating and cooling equipment shall be sized in accordance with ACCA manual S 3-2004, as listed in chapter 43, based on building loads calculated in accordance with the provisions of ACCA Manual J-2002 listed in chapter 43 or other approved heating and cooling calculation methodologies. Ductwork shall be sized in accordance with the provisions of ACCA Manual D-1995, as listed in chapter 43. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30527 Standards. Rule 527. Section M2001.1.1 of the code is amended to read as follows: M2001.1.1. Standards. Oil-fired boilers and their control systems shall be listed and labeled in accordance with UL 726 listed in chapter 43. Electric boilers and their control systems shall be listed in accordance with UL 834 listed in chapter 43. Boilers shall be designed and constructed in accordance with the requirements of the Michigan boiler code, R 408.4001 to R 408.5507. Gas-fired boilers shall conform to the requirements listed in chapter 24 of the code. 2001 AACS. R 408.30528 Terms defined in other codes. Rule 528. Section G2402.3 of the code is amended to read as follows: G2402.3. Terms defined in other codes. Where terms are not defined in the code and are defined in the Michigan electrical code, R 408.30801 to R 408.30880, Michigan building code, R 408.30401 to R 408.30547, international fire code listed in chapter 43, Michigan mechanical code, R 408.30901 to R 408.30998 or Michigan plumbing code, R 408.30701 to R 408.30796, the terms shall have the meanings ascribed to them as in those codes. History: 2001 AACS.; 2008 AACS. R 408.30529 Lining required. Rule 529. Section P2709.2 of the code is amended as follows: P2709.2. Lining required. The adjoining walls and floor framing enclosing on-site built-up shower receptors shall be lined with sheet lead, copper, or a plastic liner material that complies with ASTM D 4068 or ASTM D 4551 listed in chapter 43. The lining material shall extend not less than 3 inches (76 mm) beyond or around the rough jambs and not less than 3 inches (76 mm) above the finished thresholds. History: 2001 AACS.; 2008 AACS. R 408.30530 Requirements for discharge pipe. Rule 530. Section P2803.6.1 of the code is amended to read as follows: P2803.6.1. Requirements for discharge pipe. Relief valves shall not discharge so as to be a hazard, a potential cause of damage, or a nuisance. A relief valve discharge pipe shall be provided for each individual relief valve and shall meet all of the following: a. Shall terminate atmospherically not more than 4 inches (102 mm) from the floor with an unthreaded end. b. Shall not be interconnected. c. Valves shall not be connected in the relief valve discharge pipe. d. Shall be rigid pipe approved for water distribution, with a minimum temperature rating of 210 degrees Fahrenheit. e. Shall have the same nominal inside diameter as the relief valve outlet and shall drain by gravity flow. The outlet of a pressure, temperature, or other relief valve shall not be directly connected to the drainage system. History: 2001 AACS.; 2008 AACS. R 408.30531 Duct construction. Rule 531. Section M1601.3.1 of the code is amended to read as follows: M1601.3.1. Joints and seams. Joints of duct systems shall be made substantially airtight by means of tapes, mastics, gasketing, cleats, or other approved closure systems. Joints of duct systems located outside the building thermal envelope shall be made airtight by means of tapes, mastics, caulk, gasketing, or other approved sealants. Closure systems used with rigid fibrous glass ducts shall comply with UL 181A and shall be marked "181A-P" for pressure-sensitive tape, "181A-M" for mastic or "181A-H" for heat-sensitive tape. Closure systems sued with flexible air ducts and flexible air connectors shall comply with UL 181B and shall be marked "181B-FX" for pressure-sensitive tape or "181B-M" for mastic. Duct connections to flanges of air distribution system equipment or sheet metal fittings shall be mechanically fastened. Mechanical fasteners for use with flexible nonmetallic air ducts shall comply with UL 181B and shall be marked 181B-C. Crimp joints for round ducts shall have a contact lap of at least 1.5 inches (38 mm) and shall be mechanically fastened by means of at least 3 sheet metal screws or rivets spaced around the joint. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30532 Roof extension. Rule 532. Section P3103.1 of the code is amended to read as follows: P3103.1. Roof extension. All open vent pipes that extend through a roof shall terminate at least 1 foot (305 mm) above the roof, except that if a roof is to be used for any purpose other than weather protection, then the vent extension shall be run not less than 7 feet (2134 mm) above the roof. 2001 AACS. R 408.30533 Frost closure. Rule 533. Section P3103.2 of the code is amended to read as follows: P3103.2. Frost closure. To prevent frost closure, every vent extension through a roof shall be not less than 3 inches (76 mm) in diameter. Any increase in the size of the vent shall be made inside the building with a minimum of 1 foot (305 mm) below the roof or inside the wall. 2001 AACS. R 408.30534 Venting. Rule 534. Section P3105.1 and tables 3002.1 (1), 3002.1 (2) and 3002.2 are amended and section 3105.4Pand figure 3105.4 are added to the code and figure N3 in appendix N of the code is amended to read as follows: P3105.1. Distance of trap from vent. Each fixture trap shall have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent fitting are within the requirements set forth in table P3105.1 of the code. P3105.4. Vertical leg for waste fixture drains. A vertical leg (see figure P3105.4) is permitted within a fixture drain of a waste fixture in accordance with the following criteria: 1. Minimum trap diameter shall be in accordance with table P3201.7 of the code. 2. The diameter of section A shall be equal to the diameter of the trap. 3. The length of section A shall not be less than 8 inches (203 mm) and in accordance with table P3105.1 of the code. 4. The diameter of section B shall be 1 pipe size larger than the diameter of Section A. 5. The length of section B shall not be more than 36 inches (914 mm). 6. The diameter of section C shall be 1 pipe size larger than the diameter of section B. 7. The total length of section A and section C shall not exceed the distance allowed in table P3105.1 of the code. 8. Bends shall be the diameter of the largest connected section.
TABLE P3002.1 (1)
|
MATERIAL |
STANDARD |
|
Acrylonitrile butadiene styrene (ABS) plastic pipe |
ASTM D 2661; ASTM F 628; CSA B 181.1 |
|
Brass pipe |
ASTM B 43 |
|
Cast-iron pipe |
ASTM A 74; CISPI 301; ASTM A 888 |
|
Coextruded composite ABS DWV schedule 40 IPS pipe (solid) |
ASTM F 1488 |
|
Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core) |
ASTM F 1488 |
|
Coextruded composite PVC DWV schedule 40 IPS pipe (solid) |
ASTM F 1488 |
|
Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core) |
ASTM F 1488; ASTM F 891 |
|
Coextruded composite ABS IPS-DR, PS140, PS200 DWV |
ASTM F 1488 |
|
Coextruded composite PVC IPS-DR, PS140, PS200 DWV |
ASTM F 1488 |
|
Copper or copper-alloy pipe |
ASTM B 42; ASTM B 302 |
|
Copper or copper-alloy tubing (Type K, L, M or DWV) |
ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 306 |
|
Galvanized steel pipe |
ASTM A 53 |
|
Polyolefin pipe |
CSA B181.3 |
|
Polyvinyl chloride (PVC) plastic pipe (Type DWV) |
ASTM D 2665; ASTM D 2949; CSA B181.2; ASTM F 1488 |
|
Stainless steel drainage systems, Types 304 and 316L |
ASME A112.3.1 |
ABOVE-GROUND DRAINAGE AND VENT PIPE
TABLE P3002.1(2)
UNDERGROUND BUILDING DRAINAGE AND VENT PIPE
|
MATERIAL |
STANDARD |
|
Acrylonitrile butadiene styrene (ABS) plastic pipe |
ASTM D 2661; ASTM F 628; CSA B181.1 |
|
Asbestos-cement pipe |
ASTM C 428 |
|
Cast-iron pipe |
ASTM A 74; CISPI 301; ASTM A 888 |
|
Coextrueded composite ABS DWV schedule 40 IPS pipe (solid) |
ASTM F 1488 |
|
Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core) |
ASTM F 1488 |
|
Coextruded composite PVC DWV schedule 40 IPS pipe (solid) |
ASTM F 1488 |
|
Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core) |
ASTM F 891; ASTM F 1488 |
|
Coextruded composite ABS IPS-DR, PS140, PS200 DWV |
ASTM F 1488 |
|
Coextruded composite PVC IPS-DR, PS140, PS200 DWV |
ASTM F 1488 |
|
Copper or copper alloy tubing (Type K, L, M or DWV) |
ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 306 |
|
Polyolefin pipe |
ASTM F 1412; CSA B181.3 |
|
Polyvinyl chloride (PVC) plastic pipe (Type DWV) |
ASTM D 2665; ASTM D 2949; CSA B181.2 |
|
Stainless steel drainage systems, Type 316L |
ASME A112.3.1 |
TABLE P3002.2
BUILDING SEWER PIPE
|
MATERIAL |
STANDARD |
|
Acrylonitrile butadiene styrene (ABS) plastic pipe |
ASTM D 2661; ASTM D 2751; ASTM F 628 |
|
Asbestos-cement pipe |
ASTM C 428 |
|
Cast-iron pipe |
ASTM A 74; ASTM A 888; CISPI 301 |
|
Coextruded composite ABS DWV schedule 40 IPS pipe (solid) |
ASTM F 1488 |
|
Coextruded composite ABS DWV schedule 40 IPS pipe (cellular core) |
ASTM F 1488 |
|
Coextruded composite PVC DWV schedule 40 IPS pipe (solid) |
ASTM F 1488 |
|
Coextruded composite PVC DWV schedule 40 IPS pipe (cellular core) |
ASTM F 1488; ASTM F 891 |
|
Coextruded composite ABS IPS-DR-PS DWV, PS140, PS200 |
ASTM F 1488 |
|
Coextruded composite PVC IPS-DR-PS DWV, PS140, PS200 |
ASTM F 1488 |
|
Coextruded composite ABS sewer and drain DR-PS in PS35, PS50, PS100, PS140, PS200 |
ASTM F 1488 |
|
Coextruded composite PVC sewer and drain DR-PS in PS35, PS50, PS100, PS140, PS200 |
ASTM F 1488 |
|
Coextruded composite PVC sewer and drain PS 25, PS 50, PS 100 (cellular core) |
ASTM F 891 |
|
Concrete pipe |
ASTM C 14; ASTM C 76; CSA A 257.1M; CSA A 257.2M |
|
Copper or copper-alloy tubing (Type K or L) |
ASTM B 75; ASTM B 88; ASTM B 251 |
|
Polyethylene (PE) plastic pipe (SDR-PR) |
ASTM F 714 |
|
Polyolefin pipe |
ASTM F 1412; CSA B181.3 |
|
Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR 26, SRD35, SDR41, PS50 or PS100) |
ASTM D 2665; ASTM D 2949; ASTM D 3034; ASTM F 1412; CSA B182.2; CSA B182.4 |
|
Stainless steel drainage systems, Types 304 and 316L |
ASME A112.3.1 |
|
Vitrified clay pipe |
ASTM C 425; ASTM C 700 |
History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30535 Connection. Rule 535. Section P3111.2.2 of the code is amended to read as follows: P3111.2.2. Connection. The combination waste and vent systems shall be provided with a dry vent connected to a point within the system or the system shall connect to a horizontal drain that is vented in accordance with one of the methods specified in this chapter. Combination waste and vent systems connecting to building drains receiving only the discharge from a stack or stacks shall be provided with a dry vent. The vent connecting the combination waste and vent pipe shall extend vertically not less than 6 inches (152 mm) above the flood level rim of the highest fixture being vented before offsetting horizontally. 2001 AACS. R 408.30536 Electrical, general, electrical conductors and connections and electrical grounding. Rule 536. Sections E3301.1, E 3301.2, E3306.7, E3808.8.1, E3808.8.2, and table E3502.2 of the code are amended to read as follows: E3301.1. Applicability. The provisions of chapters 33 to 42 of the code shall establish the general scope of the electrical system and equipment requirements of the code. Chapters 33 to 42 of the code cover those wiring methods and materials most commonly encountered in the construction of 1- and 2-family dwellings and structures regulated by the code. Other wiring methods, materials, and subject matter covered in the Michigan electrical code, R 408.30801 to R 408.30880 are also allowed by the code. E3301.2. Scope. Chapters 33 to 42 of the code shall cover the installation of electrical systems, equipment, and components indoors and outdoors that are within the scope of the code, including services, power distribution systems, fixtures, appliances, devices, and appurtenances. Services within the scope of the code shall be limited to 120/240 volt, 0- to 400- ampere, single-phase systems. These chapters specifically cover the equipment, fixtures, appliances, wiring methods, and materials that are most commonly used in the construction or alteration of 1- and 2-family dwellings and accessory structures regulated by the code. The omission from these chapters of any material or method of construction provided by the Michigan electrical code, R 408.30801 to R 408.30880, shall not be construed as prohibiting the use of such material or method of construction. Electrical systems, equipment, or components not specifically covered in these chapters shall comply with the applicable provisions of the Michigan electrical code, R 408.30801 to R 408.30880. E3306.7. Conductors of the same circuit. All conductors of the same circuit and, where used, the grounded conductor and all equipment grounding conductors shall be contained within the same raceway, cable, trench or cord. TABLE E3502.2 MINIMUM SERVICE LOAD CALCULATION
|
LOADS AND PROCEDURE |
|
3 volt-amperes per square foot of floor area for general lighting and general use receptacle outlets. |
|
Plus |
|
1,500 volt-amperes total number of 20-ampere-rated small appliance and laundry circuits. |
|
Plus |
|
The nameplate volt-ampere rating of all fastened-in-place, permanently connected or dedicated circuit-supplied motors and appliances such as ranges, ovens, cooking units, clothes dryers, and water |
|
heaters. |
|
Apply the following demand factors to the above subtotal: |
|
The minimum subtotal for the loads above shall be 100% of the first 10,000 volt-amperes of the sum of the above loads plus 40% of any portion of the sum that is in excess of 10,000 volt-amperes. |
|
Plus the largest of the following: |
|
Nameplate rating(s) of the air-conditioning and cooling equipment. |
|
Nameplate rating(s) of the heating where a heat pump is used without any supplemental electric heating. |
|
Nameplate rating of the electric thermal storage and other heating systems where the usual load is expected to be continuous at the full nameplate value. Systems qualifying under this selection shall not be figured under any other category in this table. |
|
One hundred percent of nameplate rating of the heat pump compressor and 65 percent of the supplemental electric heating load for central electric space-heating systems. If the heat pump compressor is prevented from operating at the same time as the supplementary heat, the compressor load does not need to be added to the supplementary heat load for the total central electric space-heating load. |
|
Sixty-five percent of nameplate rating(s) of electric space-heating units if less than 4 separately controlled units. |
|
Forty percent of nameplate rating(s) of electric space-heating units of 4 or more separately controlled units. |
|
The minimum total load in amperes shall be the volt-ampere sum calculated above divided by 240 volts. |
E3808.8.1. Grounding of flexible metal conduit. Flexible metal conduit shall not be permitted as an equipment grounding conductor. E3808.8.2. Grounding of liquid-tight flexible metal conduit. Liquid-tight flexible metal conduit shall not be permitted as an equipment grounding conductor. History: 2001 AACS.; 2004 AACS.; 2008 AACS. R 408.30537 Separate outdoor electric space conditioning equipment. Rule 537. Section E3501.6.3 is added to the code to read as follows: E3501.6.3. Separate outdoor electric space conditioning equipment. A service disconnect for separately metered outdoor electric space conditioning equipment may be located immediately adjacent to the outdoor meter cabinet. A permanent plaque or directory shall be installed at each service disconnect location denoting the other services, feeders, and branch circuits supplying a building or structure and area served by each service, feeder, and branch circuit. History: 2001 AACS.; 2004 AACS. R 408.30538 Combustible insulation. Rule 538. Section R808.1 of the code is amended to read as follows: R808.1. Combustible insulation. Combustible insulation shall be separated a minimum of 3 inches (76 mm) from recessed lighting fixtures, fan motors, and other heat-producing devices. Exception: When heat-producing devices are listed for lesser clearances, combustible insulation complying with the listing requirements shall be separated in accordance with the conditions stipulated in the listing. Recessed lighting fixtures installed in the building thermal envelope shall be installed in accordance with the manufacturer's installation instructions. 2001 AACS. R 408.30539 Solvent cementing. Rule 539. Section P3003.14.2 of the code is amended to read as follows: P3003.14.2 Solvent cementing. Joint surfaces shall be clean and free from moisture. A primer that conforms to ASTM F 656, as listed in chapter 43, shall be applied. Solvent cement not purple in color and conforming to ASTM D 2564, CSA B137.3 or CSA B181.2, as listed in chapter 43, shall be applied to all joint surfaces. The joint shall be made while the cement is wet, and shall be in accordance with ASTM D 2855, as listed in chapter 43. Solvent-cement joints shall be permitted above or below ground. History: 2004 AACS; 2008 AACS. R 408.30540 Elevators and platform lifts. Rule 540. Sections R323.1 and R323.2 of the code are amended to read as follows: R323.1. Elevators. Where provided, passenger elevators, limited-use/limited-application elevators or private residence elevators shall comply with the Michigan elevator rules R 408.7001 to R 408.8695. R323.2. Platform lifts. Where provided, platform lifts shall comply with the Michigan elevator rules R 408.7001 to R 408.8695. History: 2004 AACS; 2008 AACS. R 408.30541 Fuel burning appliances. Rule 541. Section M1307.6 is added to the code to read as follows: M1307.6. Fuel burning appliances. Fuel burning appliances shall not be installed within 10 feet (3048 mm) of a laundry chute. History: 2004 AACS. R 408.30542 Duct insulation/floor register location. Rule 542. Section M1601.3.4 of the code is amended and section M1601.3.9 is added to the code to read as follows: M1601.3.4. Duct insulation. Duct insulation shall be installed in accordance with the following requirements: 1. A vapor retarder having a maximum permeance of 0.05 perm [(2.87 ng/(s . m2 . Pa)] in accordance with ASTM E 96, as listed in chapter 43, or aluminum foil with a minimum thickness of 2 mils (0.051 mm), shall be installed on the exterior of insulation on cooling supply ducts that pass through nonconditioned spaces conducive to condensation. 2. Exterior duct systems shall be protected against the elements. 3. Duct coverings shall not penetrate a fireblocked wall or floor. 4. All portions of the air distribution system shall be installed in accordance with section M1601 and be insulated to an installed R-5 when system components are located within the building but outside the conditioned space, and R-8 when located outside to the building. When located within a building envelope assembly, at least R-8 shall be applied between the duct and that portion of the assembly farthest from conditioned space. Exception: Exhaust air ducts and portions of the air distribution system within appliances or equipment. M1601.3.9 Floor register location. Floor registers located in room or spaces containing water closets shall be located a minimum of 3 feet from the water closet. History: 2004 AACS. R 408.30543 Boiler low-water cutoff. Rule 543. Section M2002.5 of the code is amended to read as follows: M2002.5. Boiler low-water cutoff. All steam and hot water boilers shall be protected with a low-water cutoff control. The low-water control shall automatically stop the combustion operation of the appliance when the water level drops below the lowest safe water level as established by the manufacturer. The low-water cut off on all low-pressure boilers shall be installed in accordance with the Michigan boiler rules, R 408.4001 to R 408.5507. A low-water cutoff shall be of the float or probe type or paddle-type non-reversing flow switch. History: 2004 AACS; 2008 AACS. R 408.30544 Light, ventilation and heating. Rule 544. Section R303.4.2 of the code is amended to read as follows: R303.4.2. Exhaust openings. Outside exhaust openings shall be located as not to create a nuisance. Exhaust openings shall not be directed onto walkways. Exhaust openings shall not terminate within 2 feet of a ventilated section in a soffit. History: 2004 AACS; 2008 AACS. R 408.30545 Exterior covering. Rule 545. Sections R703.7.3, R703.7.4.1, 703.7.5 and R703.7.6 and figures R703.7, R703.7.2.1, and R703.7.2.2, of the code are amended to read as follows: R703.7.3. Lintels. Masonry veneer shall not support any vertical load other than the dead load of the veneer above. Veneer above openings shall be supported on lintels of noncombustible materials and the allowable span shall not exceed the values set forth in Table R703.7.3 of the code. The lintels shall have a length of bearing not less than 4 inches (102 mm). Steel lintels shall be corrosion-resistant. R703.7.4.1. Size, spacing, and corrosion protection. Veneer ties, if strand wire, shall not be less in thickness than no. 9 U.S. gauge [(0.148 in.) (4 mm)] wire and shall have a hook embedded in the mortar joint, or if sheet metal, shall be not less than no. 22 U.S. gauge [(0.0299 in.) (0.76 mm)] by 7/8 inch (22 mm) corrugated. Each tie shall be spaced not more than 24 inches (610 mm) on center horizontally and vertically and shall support not more than 2.67 square feet (0.25 m2) of wall area. Corrosion protection shall be provided for all veneer ties as required by section R606.15.1 of the code. 703.7.5. Flashing. Approved flashing shall be installed beneath the first course of masonry above finished ground level above the foundation wall or slab and at other points of support, including structural floors, shelf angles and lintels when masonry veneers are designed in accordance with section R703.7 of the code. See section R703.8 of the code for additional requirements. R703.7.6. Weepholes. Weepholes shall be provided in the outside wythe of masonry walls at a maximum spacing of 33 inches (838 mm) on center. Weepholes shall not be less than 3/16 inch (5 mm) in diameter. Weepholes shall be located immediately above and directly on the flashing.
History: 2004 AACS.
R 408.30546 Smoke alarm locations.
Rule 546. Sections R313.4 and R313.-5 of the code are amended to read as
follows:
R313.4. Smoke alarm locations in existing buildings constructed before
November 6, 1974. Within each dwelling unit or sleeping unit, a
single-station smoke alarm shall be installed in the following locations:
1. In each sleeping room or each area directly outside the sleeping room.
2. On each floor level including the basement level.
For sleeping units with split levels and without an intervening door
between the adjacent levels, a smoke alarm installed on the upper level shall
suffice for the adjacent lower level provided that the lower level is less
than 1 full story below the upper level.
R313.5. Equipment requirements. The required equipment for smoke alarms
shall consist of the following:
1. Installation. Smoke alarm devices shall be listed and installed in
accordance with the manufacturer's installation requirements, the provisions
of the code and the provisions of NFPA 72 as listed in chapter 43.
2. Power Source. The equipment shall be operable by power from 1 of the
following primary sources.
a. The building wiring provided that such wiring is served from a
commercial source and is equipped with a battery backup. Wiring shall be
permanent and without a disconnecting switch other than as required for
overcurrent protection.
b. A non-rechargeable battery that is capable of operating the smoke alarm
in the normal condition for a life of 5 years.
c. A rechargeable battery, with proper charging, able to power the alarm
for a life of 5 years and shall be automatically recharged by an AC circuit
of the commercial light and power source.
d. A household use alarm system with battery backup listed and approved in
accordance with the household fire warning equipment provisions of NFPA 72,
as referenced in Section R313.4 of the code.
3. Audible Alarm Notification. The activation of the alarm signal shall
produce a sound that is audible in all occupiable dwelling areas.
4. Testing and Maintenance. The owner of a dwelling unit, in which
required or optional fire detection or fire protection systems equipment is
installed, shall be responsible for the proper operation, testing, and
maintenance of the equipment in accordance with the manufacturer's
instructions included with the equipment. The occupant of rental dwelling
units shall be responsible for the periodic operational testing and periodic
cleaning of the installed equipment within the rental unit in accordance with
the testing instructions provided in the manufacturer's instructions for the
equipment. If the system fails, breaks, or is out of service, it shall be
repaired and functional within 30 days.
Exception: Smoke alarms and devices installed in buildings constructed
before November 6, 1974 where an installation was approved by the appropriate
enforcing agency under regulations in effect at the time of the installation
shall be considered to comply with the provisions of the code.
History: 2005 AACS; 2008 AACS.
R 408.30547. Barrier requirements.
Rule 547. Section AG105.5 of the code is amended to read as follows.
Section AG105.5. Barrier exceptions. Spas or hot tubs with a safety cover
which complies with ASTM F 1346, as listed in section AG107 of the code,
shall be exempt from the provisions of sections AG105.2, AG105.3, and AG105.4
of the code.
History: 2004 AACS; 2008 AACS.
| Michigan.gov
Home
| DELEG | Contact | State
Web Sites | Site Map
Privacy Policy | Link Policy | Accessibility Policy | Security Policy Copyright © 2001-2010 State of Michigan |